Browser not supported

You are using an old browser that we do not support anymore. Please consider using a modern web browser such as Microsoft Edge, Google Chrome or Firefox for the best website experience.

Steel PowerLok® lid (AS 3996 Class B)

  • AS/NZS 4586 Slip Resistance Rating R10
  • IP2XD (AS 60529) protection against ingress of foreign objects when hatch is closed.
  • Lids fit into rebate at top of pit, whilst access covers must be installed in a cast in situ concrete collar.

Steel Lid (AS 3996 Class B)

  • AS/NZS 4586 Slip Resistance Rating R10
  • IP4X (AS 60529) protection against ingress of foreign objects if fitted with universal plug.
  • Lids fit into rebate at top of pit, whilst access covers must be installed in a cast in situ concrete collar.

  • AS/NZS 4586 Slip Resistance Rating R10.
  • IP4X (AS 60529) protection against ingress of foreign objects if fitted with universal plug.
  • Lids fit into rebate at top of pit, whilst access covers must be installed in a cast in situ concrete collar.

  • Increase pit depth, riser rebate is identical to pit rebate and with lid, offers the same IP protection.
  • Can be cut to required height. Each riser adds 300mm depth.
  • ACO recommends no more than 2 risers.
  • Excellent strength to weight ratio and electrical resistivity
  • Low porosity
  • High resistance to chemicals, weathering and biological attack
  • Holesaw guides for conduit entry - holes can be cut anywhere on side walls.
  • Maximum number of holes recommended per pit is limited by conduit quantity and size.
  • Contact ACO for guidance.

All access covers have IP4X (AZ 60529) protection against ingress of foreign objects. Rhinocast® access covers offer water and gas tightness to AS 3996.

  1. Steel Urbanfil® recessed cover (AS 3996 Class B)
  2. Steel Pavermate® recessed cover (AS 3996 Class B)
  3. Steel frame - external dim. 1030 x 580 x 70mm
  4. Cast-in-situ concrete collar

  1. Ductile iron Rhinocast® solid top cover (AS 3996 Class B) AS/NZS 4586 Slip Resistance Rating R10
  2. Ductile iron Rhinocast® recessed cover (AS 3996 Class B)
  3. Iron frame - external dim. 1050 x 560 x 55mm
  4. Cast-in-situ concrete collar
  5. Ductile iron Rhinocast® solid top cover (AS 3996 Class D) AS/NZS 4586 Slip Resistance Rating R10
  6. Ductile iron Rhinocast® recessed cover (AS 3996 Class D or G)
  7. Iron frame - Class D external dim. - 1115 x 665 x 100mm Class G external dim. - 1135 x 685 x 125mm
  8. Cast-in-situ concrete collar
DescriptionPart No.Weight (kg)
Type 95 Polymer Concrete Pit7484584
Type 95 Polymer Concrete Riser (adds 300mm to pit depth)7486145

Lids & CoversPart No.Cover Wt (kg)¹Total Wt (kg)
Polymer Concrete Lid (AS 3996 Class A) - Blank748862929
Polymer Concrete Lid (AS 3996 Class A) - Communications748932929
Polymer Concrete Lid (AS 3996 Class A) - Electricity749042929
Steel Lid (AS 3996 Class B)795202020
Steel PowerLok® Lid (AS 3996 Class B)²795302525
Steel Urbanfil® recessed cover (AS 3996 Class B)³816611826
Steel Pavermate® recessed cover (AS 3996 Class B)³813382028
Ductile Iron Rhinocast® recessed cover (AS 3996 Class B)*851194563
Ductile Iron Rhinocast® solid top cover (AS 3996 Class B)*852084883
Ductile Iron Rhinocast® recessed cover (AS 3996 Class D)*8912472130
Ductile Iron Rhinocast® solid top cover (AS 3996 Class D)*8921580139
Ductile Iron Rhinocast® recessed cover (AS 3996 Class G)*87082145216

Notes:

  1. Lid and access cover weights are provided as lifting weight (individual cover parts) and total weight. Recessed cover weights do not included pavement infill; for approx. lifting weight - Urbanfil®/Pavermate® covers - multiply weight by 7; Rhinocast® covers multiply weight by 1.5.
  2. All lids are supplied with brackets and support bars where applicable. PowerLok® lids supplied with locking bolt (padlock not supplied).
  3. Optional brass edging (Specify 'BE' after part number).
  4. Optional locking, brass or stainless steel edging in 12mm or 40mm heights (Specify 'BE' or 'SS' and height after part number).
Internal Working Area(mm)
A825
B367
X876
Y418
Z520
Overall Dimensions (mm)
L978
W510
D588

Notes:

  1. Using risers will increase pit depth (Z & D) by depth of riser.
  2. Access covers will increase depth of pit by height of concrete collar - allowance should be made for concrete collar during pit installation.

Documents